MV Switches & Disconnectors

MV Switches & Disconnectors

SF6 GAS DISCONNECTORS;

ASTOR brand SF6 Gas Disconnectors have been designed to have a sealed pressure structure that does not require additional SF6 gas for 30 years in accordance with TS EN 62271-102 standard.

Technical Specifications

TECHNICAL SPECIFICATIONS OF SF6 GAS DISCONNECTORS

TECHNICAL PARAMETERSTYPEACBS36ACBS24
RATED VOLTAGERATED VOLTAGE (kV)36 kV24 kV
INSULATION VOLTAGEINSULATION VOLTAGE (kV)70 kV (rms/1 min.)50 kV (rms/1 min.)
LIGHTNING IMPULSE WITHSTAND VOLTAGELIGHTNING IMPULSE WITHSTAND VOLTAGE (kV)170 (peak 1.2–50 μs)125 (peak 1.2–50 μs)
RATED CURRENTRATED CURRENT (A)630 A630 A
RATED FREQUENCYRATED FREQUENCY (Hz)50 Hz50 Hz
SHORT CIRCUIT WITHSTAND CURRENTSHORT CIRCUIT CURRENT (kA)16–20 kA16–20 kA
RATED PEAK WITHSTAND CURRENTPEAK WITHSTAND CURRENT (kA)40 kA40 kA
SHORT CIRCUIT DURATIONSHORT CIRCUIT DURATION1 sec.1 sec.
CLASSCLASSE3, M1E3, M1

SF6 GAS DISCONNECTOR TECHNICAL SPECIFICATIONS

PARAMETERSPECIFICATIONACBS36ACBS24
RATED VOLTAGERATED VOLTAGE (kV)36 kV24 kV
INSULATION VOLTAGEPOWER FREQUENCY WITHSTAND VOLTAGE (kV)70 kV (rms / 1 min.)50 kV (rms / 1 min.)
LIGHTNING IMPULSE WITHSTAND VOLTAGELIGHTNING IMPULSE WITHSTAND VOLTAGE (kV)170 (peak 1.2–50 μs)125 (peak 1.2–50 μs)
RATED CURRENTRATED CURRENT (A)630 A630 A
RATED FREQUENCYRATED FREQUENCY (Hz)50 Hz50 Hz
SHORT-CIRCUIT WITHSTAND CURRENTSHORT-CIRCUIT CURRENT (kA)16–20 kA16–20 kA
PEAK WITHSTAND CURRENTRATED PEAK WITHSTAND CURRENT (kA)40 kA40 kA
SHORT-CIRCUIT DURATIONRATED SHORT-CIRCUIT DURATION1 sec.1 sec.
CLASSCLASSE3, M1E3, M1

SF6 GAS LOAD BREAK SWITCH TECHNICAL SPECIFICATIONS

PARAMETERSPECIFICATIONACBS36ACBS24
RATED VOLTAGERATED VOLTAGE (kV)36 kV24 kV
INSULATION VOLTAGEPOWER FREQUENCY WITHSTAND VOLTAGE (kV)70 kV (rms/1 min.)50 kV (rms/1 min.)
LIGHTNING IMPULSE WITHSTAND VOLTAGELIGHTNING IMPULSE WITHSTAND VOLTAGE (kV)170 (peak 1.2–50 μs)125 (peak 1.2–50 μs)
RATED CURRENTRATED CURRENT (A)630 A630 A
RATED FREQUENCYRATED FREQUENCY (Hz)50 Hz50 Hz
SHORT-CIRCUIT WITHSTAND CURRENTSHORT-CIRCUIT CURRENT (kA)16–20 kA16–20 kA
PEAK WITHSTAND CURRENTRATED PEAK WITHSTAND CURRENT (kA)40 kA40 kA
SHORT-CIRCUIT DURATIONRATED SHORT-CIRCUIT DURATION1 sec.1 sec.
CLASSCLASSE3, M1E3, M1

EARTHING SWITCHES TECHNICAL SPECIFICATIONS

PARAMETERSPECIFICATIONACBS36ACBS24
RATED VOLTAGERATED VOLTAGE (kV)36 kV24 kV
SHORT-CIRCUIT WITHSTAND CURRENTSHORT-CIRCUIT CURRENT (kA)16 kA16 kA
PEAK WITHSTAND CURRENTRATED PEAK WITHSTAND CURRENT (kA)40 kA40 kA
SHORT-CIRCUIT DURATIONRATED SHORT-CIRCUIT DURATION1 sec.1 sec.
CLASSCLASSE2E2

Take action to find solutions that will carry your power into the future.

With over 21 years of experience in the industry, our superior quality standards, and our engineering-driven approach, we are here for you.